2024年8月5日发(作者:)

Functional safety manual
Liquiphant M/S with FEL58
and Nivotester FTL325N
Level Limit Measuring System
Application
Overfill protection or operating maximum detection of
all types of liquids in tanks to satisfy particular safety
systems requirements to IEC61508/IEC61511-1.
The measuring device fulfils the requirements
concerning
•For safety functions up to SIL 2
•Explosion protection by intrinsic safety or flameproof
enclosure
•EMC to EN 61326 and NAMUR Recommendation
NE 21
Your benefits
•For overfill protection up to SIL 2
–Independently assessed (Functional Assessment)
by to IEC61508/IEC61511-1
•Monitoring for corrosion on the tuning fork of the
sensor
•No calibration
•Fault message for circuit break and short-circuit
•Functional test of subsequent devices at the push of a
button
•Protected against outside vibration
•Easy commissioning
SD161F/00/EN/02.10
71110409
Table of contents
SIL declaration of conformity. . . . . . . . . . . . . . . . . . . .3
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
General depiction of a safety system (protection function) . . . . . . . 4
Structure of the measuring system with
Liquiphant M/S (FEL58) and Nivotester FTL325N . . .5
Level limit measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Supplementary device documentation . . . . . . . . . . . . . . . . . . . . . . 6
Settings and installation instructions . . . . . . . . . . . . . .7
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Response in operation and failure. . . . . . . . . . . . . . . .8
Recurrent function tests of the measuring system. . . .8
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Specific values and wiring options for the measuring system
Liquiphant M/S (FEL58) and Nivotester FTL325N . . . . . . . . . . . . 9
Exida Management Summary . . . . . . . . . . . . . . . . . .16
Supplementary Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2
SIL declaration of conformity
SIL-03001D_00_A2
3
Introduction
!
General depiction of
a safety system
(protection function)
Note!
For general informationen about SIL please refer to: /sil
Parameter tables for determining Safety Integrity Level (SIL)
The following tables are used to define the reachable SIL, the requirements pertaining to the “Average
Probability of Dangerous Failure on Demand” (PFD
avg
), the “Hardware Fault Tolerance” (HFT) and the “Safe
Failure Fraction” (SFF) of the safety system. The specific values for the Liquiphant M/S + Nivotester FTL325N
measuring system can be found in the Appendix.
Permitted probabilities of dangerous failures on demand of the complete safety related system dependent on
the SIL (e.g. exceeding a defined MAX level/switch point) (Source: IEC 61508, Part 1):
SIL
4
3
2
1
PFD
avg
≥ 10
−5
...< 10
−4
≥ 10
−4
...< 10
−3
≥ 10
−3
...< 10
−2
≥ 10
−2
...< 10
−1
The following table shows the achievable Safety Integrity Level (SIL) as a function of the probability fraction of
safety-oriented failures and the "hardware fault tolerance" of the complete safety system for type B systems
(complex components, not all faults are known or can be described).
SFFHFT
0 1(0)
1)
< 60 %
60 % ...< 90 %
90% ...<99%
99 %
1)
not allowed
SIL 1
SIL 2
SIL 3
SIL 1
SIL 2
SIL 3
2 (1)
1
SIL 2
SIL 3
In accordance with IEC 61511-1 (FDIS) (Section 11.4.4), the HFT can be reduced by one
(values in brackets) if the devices used fulfil the following conditions:
- the device is proven in use,
- only process-relevant parameters can be changed at the device (e.g. measuring range, ... ),
- changing the process-relevant parameters is protected (e.g. password, jumper, ... ),
- the safety function requires less than SIL 4.
All conditions apply to Liquiphant M/S + Nivotester FTL325N.
4
Structure of the measuring system with
Liquiphant M/S (FEL58) and Nivotester FTL325N
Level limit measuring systemThe measuring system's devices are displayed in the following diagram (example).
LiquiphantM/S
[Exia]
CH1
[Exia]
CH1CH2
FEL
Electronicinsert
CH3
FTL325N
FTL325N
CH1
CH1CH2CH3
Nivotester
FTL325N
(1and3channel)
SD161Fen02
Safety functionThe safety function applies to all settings in MAX safety (monitoring of the covered state) and use of the NO
contacts of the level relays.
The following settings are permitted for the safety function:
Device
Liquiphant
Setting
Density switch setting: 0.5
Density switch setting: 0.7
"MAX" safety
Nivotester
FTL325N-#3#3
Error current signal < 1.2 mA
As-delivered state
Density switch setting: 0.7
"MAX" safety
Error current signal < 1.2 mA
All settings except "ΔS function" Three-channel operation
(see Section Settings and installation instructions)
The DIL switch for failure indication
(short-circuit and cable break monitoring)
must be set into position ON.
Failure switch "ON"
Nivotester
FTL325N-#1#1
Error current signal < 1.2 mAError current signal < 1.2 mA
One-channel operation
The DIL switch for failure indication
(short-circuit and cable break monitoring)
must be set into position ON.
Failure switch "ON"
The level relay always works in quiescent current safety; i.e. the relay releases when:
•the switch point is exceeded (level exceeds response height)
•a fault occurs
•the mains voltage fails
In addition to the level relay, the alarm relay works in quiescent current safety and releases when:
•one of the following faults occurs:
–the sensor connection is interrupted
–the sensor connection short circuits
•the mains voltage fails
!
Note!
When the alarm relay releases, the level relay also releases.
5
Permitted combinations of Nivotester FTL325N with Liquiphant M/S for the safety function
The following combinations are permitted for the measuring system:
Nivotester
One-channel device
FTL325N-H###
FTL325N-P###
FTL325N-T###
FTL325N-W###
Three-channel device
FTL325N-H###
FTL325N-P###
FTL325N-T###
FTL325N-W###
FTL50-######8###*
FTL51-######8###*
FTL50H-######8###*
FTL51H-######8###*
FTL51C-######8####*
FTL70-######8####*
FTL71-######8####*
Liquiphant M + FEL58Liquiphant S + FEL58
Permitted device types (# = all device versions permitted); * 8 = FEL58
Safety function data
The mandatory settings and data for the safety function can be found in the Appendix (Page 9).
The measuring system reacts in ≤ 0.9 s.
!
Supplementary
device documentation
Note!
MTTR is set at eight hours.
Safety systems without a self-locking function must be monitored or set to an otherwise safe state after
carrying out the safety function within MTTR.
The following must be available for the measuring system:
Technical Information
Nivotester FTL325NFor all device types:
TI353F
Types FTL50, FTL51,
FTL50H, FTL51H:
TI328F
Operating Instructions
One-channel device FTL325N-#1#1: KA170F
Three-channel device FTL325N-#3#3: KA171F
Types FTL50, FTL51: KA143F
Types FTL50, FTL51: KA163F
(with aluminium housing/separate terminal
compartment)
Types FTL50H, FTL51H: KA144F
Types FTL50H, FTL51H: KA164F
(with aluminium housing/separate terminal
compartment)
Type FTL51C:
TI347F
Type FTL51C: KA162F
Type FTL51C: KA165F
(with aluminium housing/separate terminal
compartment)
Types FTL70, FTL71: KA172F
Types FTL70, FTL71: KA173F
(with aluminium housing/separate terminal
compartment)
Setting, configuration, remarks,
function tests
Liquiphant M
Liquiphant SFor all device types:
TI354F
Relevant contentsConnection data,
Installation instructions
6
Settings and installation instructions
Installation instructionsPlease refer to the Operating Instructions (KA) for information regarding the correct installation of
Liquiphant M/S + Nivotester FTL325N.
Since the application conditions have an effect on the safety of the measurement, pay attention to the notes in
the Technical Information (TI) and Operating Instructions (KA).
The ambient conditions for the Nivotester FTL325N must correspond to IP54 (in accordance with EN 60529).
Refer to the following documentation for instructions on setting the devices:
Device
Liquiphant M/S (FEL58)
Nivotester FTL325N-#1#1
Nivotester FTL325N-#3#3
Setting description in documentation:
KA143F, KA163F, KA144F, KA164F, KA162F,
KA165F, KA172F, KA173F, *
KA170F
KA171F
(* type-dependent, see table: Supplementary device documentation, Page 6)
Settings for Liquiphant M/S (FEL58):
•The density switch setting must be configured according to the density range of the medium.
•The setting of the safety mode has an effect on the function. The DIL switch must be set to MAX in a SIL
application.
Settings for Nivotester FTL325N-#3#3 (three-channel version):
SettingDescription
Channels 2+3 in
ΔS function
Ds
CH3
SD161Fxx03
"
Caution!
CH2
THIS SETTING IS NOT PERMITTED FOR THE
SAFETY FUNCTION
Channel 1, independent
CH1
CH2
CH3
SD161Fxx04
Channel 1 is permitted for the safety function.
The DIL switch for fault messaging
(short-circuit and cable break monitoring)
must be set into position ON.
CHANNELS 2 AND 3 IN THIS SETTING ARE NOT
PERMITTED FOR THE SAFETY FUNCTION
Ds
Channels 2+3 in
ΔS function
"
"
Caution!
Observe the following for the Nivotester FTL325N-####: The operator must use suitable measures
(e.g. current limiter, fuse) to ensure the relay contact characteristics are not exceeded:
•U ≤ 253 V AC 50/60 Hz , I ≤ 2 A, P ≤ 500 VA at cos ϕ ≥ 0.7 or
•U ≤ 40 V DC, I ≤ 2 A, P ≤ 80 W
Caution!
Changes to the measuring system and settings after start-up can impair the protection function!
7
Response in operation and failure
The response in operation and failure is described in the following documentation.
Device
Liquiphant M/S (FEL58)
Nivotester FTL325N-#1#1
Nivotester FTL325N-#3#3
Setting description in documentation:
KA143F, KA163F, KA144F, KA164F, KA162F,
KA165F, KA172F, KA173F, *
KA170F
KA171F
(* type-dependent, see table: Supplementary device documentation, Page 6)
Recurrent function tests of the measuring system
The operativeness of the overfill protection must be checked annually if the PFD
avg
values given in the
Appendix are used.
The check must be carried out in such a way that it is proven that the overfill protection functions perfectly in
interaction with all components. This is guaranteed when the response height is approached in a filling process.
If it is not practical to fill to the response height, suitable simulation of the level or of the physical measuring
effect must be used to make the level sensor respond. If the operativeness of the level sensor/transmitter can
be determined otherwise (exclusion of faults that impair function), the check can also be completed by
simulating the corresponding output signal.
In the case of recurrent tests, each permitted setting must be checked, especially whether all the alarm switches
are set to ON.
"
Caution!
Note the following points for the function test:
•Each individual channel must be by approaching the level.
•Relay contact switching can be checked by using a hand multimeter at the terminals or by observing the
overfill protection elements (e.g. horn, adjuster).
•In multi-channel devices, all channels which do not carry out a safety function must be included in the
recurrent function tests if faulty functioning cannot be detected by any other means.
•As a positive test result, a covered tuning fork must be detected and trigger the alarm for overfill protection.
•If fork covering is not detected during the recurrent test, the monitored process must be set to a
safe state by means of additional or other measures and/or kept in the safe state until the safety
system is repaired.
8
Appendix
Specific values and
wiring options for
the measuring system
Liquiphant M/S (FEL58)
and Nivotester FTL325N
The tables show the specific values and wiring options for the measuring system.
Note!
Note the following points on the tables below:
•The PFD
avg
values for multichannel systems already contain common cause failures for the associated wiring
scheme.
•The PFD
avg
values are only valid for the associated wiring scheme. Wiring schemes other than those shown
in the Appendix were not assessed and thus do not bear any information relevant to safety.
Using NC contacts instead of NO contacts requires further consideration of the installation means.
•The wiring scheme shows the number of devices (Liquiphant and Nivotester) and the limit relay contact
circuits (open, when the sensor signals covering).
•For every channel, which performs a safety function, the failure indication (cable break/short circuit) must
be switched on.
•With several devices in a wiring scheme, they all indicate the same displayed settings.
Warning!
For safety related use of the Liquiphant S for MAX detection, the following application errors must be excluded:
•Hydrogen diffusion at temperatures over 180 °C and over 64 bar.
#
9
1oo1 architecture (CONF 1)
Liquiphant (FEL58)
Settings
Evaluated NAMUR transmitter
Error current signal
< 1.2 mA
1) density 0.7 / 0.5
2) MAX safety
SD161Fxx05
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
SIL 2
0
82.5 %
2.6 x 10
-4
CH1
SD161Fxx06
Ask the manufacturer in question for the NAMUR transmitter parameters
relevant to safety.
Recurrent test
e.g. approaching level
** TI (test interval) = annual
1oo1D structure
P
F
D
a
v
g
3,00E-03
2,50E-03
2,00E-03
1,50E-03
1,00E-03
5,00E-04
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen07
PFD
10
1oo1 architecture (CONF 2)
Liquiphant (FEL58)
Settings
Nivotester FTL325N-#1#1
Settings
(One-channel device)
1) density 0.7 / 0.5
2) MAX safety
Error current signal
< 1.2 mA
SD161Fxx05
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
SIL 2
0
89.8 %
3.1 x 10
-4
CH1
CH1:
SD161Fxx08
Recurrent test
e.g. approaching level
** TI (test interval) = annual
1oo1D structure
P
F
D
a
v
g
3,50E-03
3,00E-03
2,50E-03
2,00E-03
1,50E-03
1,00E-03
5,00E-04
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen09
PFD
11
1oo1 architecture (CONF 3)
Liquiphant (FEL58)
Settings
Nivotester FTL325N-#3#3
Settings
(Three-channel device)
1) density 0.7 / 0.5
2) MAX safety
Error current signal
< 1.2 mA
SD161Fxx05
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
SIL 2
0
89.5 %
3.5 x 10
-4
CH1
CH2
CH3
CH2orCH3:
SD161Fen10
Recurrent test
e.g. approaching level
** TI (test interval) = annual
1oo1D structure
P
F
D
a
v
g
4,00E-03
3,50E-03
3,00E-03
2,50E-03
2,00E-03
1,50E-03
1,00E-03
5,00E-04
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen11
PFD
12
1oo2 architecture (CONF 4)
Liquiphant (FEL58)
Settings
Nivotester FTL325N-#3#3
Settings
(Three-channel device)
1) density 0.7 / 0.5
2) MAX safety
Error current signal
< 1.2 mA
SD161Fxx12
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
SIL 2
1
89.5 %
1.8 x 10
-5
CH1
CH2
CH3
CH1 + CH2 or CH1 + CH3:
SD161Fen13
Recurrent test
e.g. approaching level
** TI (test interval) = annual
1oo2D structure
P
F
D
a
v
g
2,50E-04
2,00E-04
1,50E-04
1,00E-04
5,00E-05
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen14
PFD
13
2oo3 architecture (CONF 5)
Liquiphant (FEL58)
Settings
Nivotester FTL325N-#3#3
Settings
(Three-channel device)
1) density 0.7 / 0.5
2) MAX safety
Error current signal
< 1.2 mA
SD161Fxx15
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
CH1
CH2
CH3
SIL 2
1
89.9 %
2.0 x 10
-5
SPS
2oo3
SD161Fxx16
Recurrent test
e.g. approaching level
** TI (test interval) = annual
2oo3D structure
P
F
D
a
v
g
3,00E-04
2,50E-04
2,00E-04
1,50E-04
1,00E-04
5,00E-05
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen17
PFD
14
1oo1 architecture (CONF 6)
Liquiphant (FEL58)
Settings
Nivotester FTL325N-#3#3
Settings
(Three-channel device)
1) density 0.7 / 0.5
2) MAX safety
Error current signal
< 1.2 mA
Ds
SD161Fxx18
CH1
CH2
CH3
SIL
HFT
SFF
PFD
avg
**
Wiring scheme
SIL 2
0
89.8 %
3.1 x 10
-4
CH1
CH2
CH3
SIL
CH1:
SD161Fxx19
Recurrent test
e.g. approaching level
** TI (test interval) = annual
1oo1D structure
P
F
D
a
v
g
3,50E-03
3,00E-03
2,50E-03
2,00E-03
1,50E-03
1,00E-03
5,00E-04
0,00E+00
0,0 2,0 4,0 6,0 8,0 10,0
Test interval
[years]
SD161Fen09
PFD
15
Exida Management Summary
L00-FTL325Nx-01-06-xx-en-004
L00-FTL325Nx-01-06-xx-en-003
16
L00-FTL325Nx-01-06-xx-en-006
L00-FTL325Nx-01-06-xx-en-005
17
L00-FTL325Nx-01-06-xx-en-007
18
Supplementary
Documentation
Safety in the Process Industry – reducing risks with SIL
CP002Z/11
19
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel.+41 61 715 81 00
Fax+41 61 715 25 00
***************.com
SD161F/00/EN/02.10
71110409
FM+SGML 6.0 ProMoDo
71110409
本文发布于:2024-08-05 15:32:58,感谢您对本站的认可!
本文链接:https://www.4u4v.net/it/1722843178292329.html
版权声明:本站内容均来自互联网,仅供演示用,请勿用于商业和其他非法用途。如果侵犯了您的权益请与我们联系,我们将在24小时内删除。
| 留言与评论(共有 0 条评论) |